Wuhan GDZX Power Equipment Co., Ltd sales@gdzxdl.com 86--17362949750
In the power operation and maintenance field, the ZXZK-3C is an authoritative device for testing the "vacuum integrity" of vacuum interrupters (vacuum tubes). The quality of its manufacturing process directly determines whether it can accurately measure extremely small ion currents in the range of 10⁻²Pa to 10⁻⁵Pa under strong electromagnetic interference.![]()
The core principle of the ZXZK-3C is magnetron discharge: by applying high voltage between the contacts of the vacuum interrupter and passing a pulsed current through the coil to generate a synchronous magnetic field, the residual gas inside the interrupter is ionized.
The manufacturing process of a high-quality ZXZK-3C should focus on the following three "invisible" aspects:
| Project | Process Requirements Standard Values: | Why is this value important? |
|---|---|---|
| Vacuum Measurement Range | 10⁻⁵ Pa ~ 10⁻¹ Pa | It covers the entire lifecycle of a vacuum circuit breaker, from "excellent" to "retirement." |
| Measurement Accuracy | ≤ 5% (10⁻⁴ ~ 10⁻¹ Pa) | An error exceeding 5% can mislead maintenance personnel in assessing the lifespan of the arc-extinguishing chamber. |
| Current Sampling Resolution | ≤ 0.1 µA (nanoampere level) | The ion current is extremely weak; low resolution means that small currents are directly drowned out by system noise. |
| Magnetic Control Current Output | Pulse type, ≥ 300A (adjustable) | An insufficiently weak magnetic field cannot effectively excite ions; the pulsed current needs precise synchronization.This demands excellent drive circuit design. |
| High Voltage Output | Pulse high voltage, ≤ 30kV | To provide sufficient potential energy to break down the arc-extinguishing chamber gap, extremely high insulation strength of the high-voltage module is required. |
Besides the performance parameters mentioned above, the quality of the manufacturing process depends on the control capabilities of the following hardware parameters:
As the purchaser or technical manager, when evaluating a manufacturer's manufacturing processes, you can request to see the following three "hardcore" documents: